- 41KW EVI Air to water heat pump
- 【Brief】:operation in cold weather -25℃ max outlet hot water temp +55℃ for sanitary hot water and under floor
- 【Series】:Monoblock Low temperature EVI heat pump
- Description
-
Monoblock Low temperature EVI Air to water heat pump price list
Model
heat pump
FA-10EVI
Unit function
Standard condition
Heating capacity
kw
40.60
kcal/h
34910.00
Hot water supply
T/h
0.87
Input power
kw
9.60
Low temperature conditions
Heating capacity
kw
33.20
kcal/h
28547.00
Hot water supply
T/h
0.63
Input power
kw
9.38
Ultra-low temperature conditions
Heating capacity
kw
19.40
kcal/h
16681.00
Hot water supply
T/h
0.37
Input power
kw
9.30
Standard condition heating input current
A
16.80
Max running current
A
21.00
Power
V/Ph/Hz
380V~415/3N/60hz
Unit Noise comprehensive index
Db(A)
62.00
Dimension
W
mm
1450.00
D
mm
780.00
H
mm
1050.00
Unit weight
kg
270.00
Running control
Water temperature control precision
℃
±2℃
Ambient temperature range
℃
–25℃ – 43℃
Refrigerants circulation structure
Throttle type
thermostatic expansion valve/electric expansion valve
Refrigerant
Type
R407C,R410A
Refrigerant charge
kg
3.5*2
Max working pressure
bar
28.00
Compressor
Type
Efficient fully enclosed type vortex. Copeland,panasonic EVI
Stall Current
A
60.00
Air-source side heat exchanger
Type
Finned heat exchanger
Qty
pc
2.00
Motor power
kw
0.4*2
Hhot water side heat exchanger
Type
tube in shell heat exchange/plate heat exchange
Water flow
m3/h
6.98
Water pressure down
kPa
36.00
Connecting pipe size
DN
32.00
Water side max working pressure
kPa
1000.00
1,standard condition heating condiiton: air source side heat exchanger inlet air 20/15℃,hot water source intial temp 15℃,end heating temp 55℃.
2,Low temp heating condition: air source side heat exchanger inlet air 7/6℃,hot water side intial temp 10℃,end heating temp 55℃.
3,Ultra-low temperature heating conditions:air-source side heat exchanger inlet air -15/-17℃,hot water side intial temp 10℃,end heating temp 55℃.