- 34.6 kw EVI air to water heat pump EVI low temperature air source heat pump( heating/cooling )
- 【Brief】:Monoblock Low temperature EVI heat pump
- 【Series】:Monoblock Low temperature EVI heat pump
- Description
-
EVI air to water heat pump( heating/cooling)
MODEL
UNIT
FAC-10EVI
Cooling(1)
cooling capacity
kW
27.98
BTU/h
95495
input power
kW
9.32
Heating(2)
heating capacity
kW
34.6
BTU/h
118089
input power
kW
9.22
Heating(3)
heating capacity
kW
19.16
BTU/h
65392
input power
kW
8.24
Rated input current
A
16.8
max input current
A
24
Power supply
V/Ph/Hz
380V/3N/50Hz
Nosie
dB(A)
62
Dimension
width
mm
1450
deepth
mm
780
height
mm
1050
Unit weight
kg
270
operating range
℃
minus 25~43℃
Throttling type
thermal expansion valves/electric expansion valve
Refrigerant
R407C,R410A
compressor
Type
copeland /panasonic EVI
Air source heat exchanger
Type
Finned heat exchange
qty
piece
2
motor power
kW
0.4*2
Hot water side heat exchange
type
Tube in shell heat exchange/plate heat exchange
water flow
m3/h
5.78
water pressure down
kPa
36
pipe size
inch
1-1/4
water side max working pressure
kPa
1000
1. Rated cooling working condition: air inlet temp is 35℃. Water inlet temp is 12℃, Water outlet temp is 7℃.
2. Rated heating working condition: air inlet dry bulb temp is 7℃, wet bulb temp is 6℃. Water inlet temp is 40℃, Water outlet temp is 45℃.
3. Colder heating working condition: air inlet dry bulb temp is -15℃, wet bulb temp is -17℃. Water inlet temp is 40℃, Water outlet temp is 45℃.