- 15KW EVI low temp heating and cooling air source heat pump water heater
- 【Brief】:
- 【Series】:EVI heating and cooling
- Description
-
EVI air to water heat pump( heating/cooling)
MODEL
UNIT
FAC-05EVI
Cooling(1)
cooling capacity
kW
14.49
BTU/h
49454
input power
kW
7.94
Heating(2)
heating capacity
kW
17.8
BTU/h
60751
input power
kW
7.85
Heating(3)
heating capacity
kW
10.08
BTU/h
34403
input power
kW
6.99
Rated input current
A
8.4
max input current
A
12
Power supply
V/Ph/Hz
380V/3N/50Hz
Nosie
dB(A)
58
Dimension
width
mm
810
deepth
mm
780
height
mm
1050
Unit weight
kg
145
operating range
℃
minus 25~43℃
Throttling type
thermal expansion valves/electric expansion valve
Refrigerant
R407C,R410A
compressor
Type
copeland /panasonic EVI
Air source heat exchanger
Type
Finned heat exchange
qty
piece
1
motor power
kW
0.4
Hot water side heat exchange
type
Tube in shell heat exchange/plate heat exchange
water flow
m3/h
2.89
water pressure down
kPa
30
pipe size
inch
1
water side max working pressure
kPa
1000
1. Rated cooling working condition: air inlet temp is 35℃. Water inlet temp is 12℃, Water outlet temp is 7℃.2. Rated heating working condition: air inlet dry bulb temp is 7℃, wet bulb temp is 6℃. Water inlet temp is 40℃, Water outlet temp is 45℃.3. Colder heating working condition: air inlet dry bulb temp is -15℃, wet bulb temp is -17℃. Water inlet temp is 40℃, Water outlet temp is 45℃.