- Description
-
Air to water heat pump/air cooled mini chiller (Heating and cooling)
Model
heatpump
FAC-02
Unit functions
Rated heating
Heating capacity
kW
6.3
Btu/h
21502
Rated power
kW
1.65
Rated current
A
3.58
Rated cooling
Cooling capacity
kW
5.5
Btu/h
18771
Rated power
kW
1.67
Rated current
A
3.55
Max ruuning current
A
10
Power
V/Ph/Hz
220V~240/1N/50Hz/60hz
Noise
dB(A)
40
Size
L(A)
mm
750
w(B)
mm
300
H(C)
mm
510
Weight
kg
65
Operating control
Precision temp precision
℃
±1℃
Operation range
℃
— 20℃~45℃
Operation panel
Type
LCD
Main functions
Operating mode,temperature,operating condition, timing
Throttling
Electronic expansion valves
The outlet temp
℃
60℃
Refrigerate
Type
R410A, R407C
Compressor
Type
hitachi panasoni
Air side heat exchange
Type
Finned heat exchange
Qty
pc
1
Fan type
Type
Axial big twist angle fan
Motor power
w
40
Water side heat exchange
Type
tube in shell heat exchanger
Water flow(summer)
m3/h
1
Water flow(winter)
m3/h
1.25
Water pressure down
kpa
20
Connection dimension
Inch
0.75 Water side max working pressure
KPA
1000
Rated cooling working conditions: air side return air temp 35℃, use side input water temp is 12℃, outlet water temp is 7℃
Rated heating working conditions: air side return air dry ball temp is 7℃, wet ball temp is 6℃, use side input water temp 40℃, outlet water temp is 45℃