split type EVI Low temp heat pumpCurrent Location :Home > PRODUCTS> EVI Low temp air source heat pump> split type EVI Low temp heat pump
- Description
-
SPLIT AIR TO WATER EVI HEAT PUMP Model FA-12EVIS Heating capacity * 35 Heating power input * 7.99 Heating capacity ** 25.4 Heating power input ** 7.98 Heating capacity *** 18.4 Heating power input *** 7.91 Heating capacity **** 17.1 Heating power input **** 7.89 Heating capacity ***** 29.20 Heating power input ***** 12.44 COP* 4.32 COP** 3.18 COP*** 2.33 COP**** 2.17 COP***** 2.35 Cooling capacity 29.80 Cooling power input 11.88 EER 2.51 Max. water temperature 60 Rated water temperature 55 Water flow 5.6 Water pressure drop 40 Water connections 1.5 Built-in water pump no Build in electrict heater Optional Air flow 12000 Fan qty 2 Fan rated power 250*2 Noise 58 Compressor Copeland (EVI) 1 Power supply 380~400V/3PH/50Hz Refrigerant R407C Type of defrosting Reverse circulation Net weight (outdoor unit) 280 Gross weight (outdoor unit) 300 Net dimensions (outdoor unit) 1450*780*1050 Packing dimensions (outdoor unit) 1550*880*1150 Net weight (indoor unit) 40 Gross weight (indoor unit) 43 Net dimensions (indoor unit) 500*260*840 Packing dimensions (indoor unit) 520*280*870 Expansion tank yes Unit working temperature : -25℃ to 43℃
2. *Test condition: ambient temp: 7℃/6℃, water inlet/outlet: 30℃/35℃
** Test condition: ambient temp: -2℃/-1℃, water inlet/outlet: 30℃/35℃
***Test condition: ambient temp: -15℃/-℃, water inlet/outlet: 30℃/35℃
**** Test condition: ambient temp: -20℃/-℃, water inlet/outlet: 30℃/35℃
***** Test condition: ambient temp: 7℃/6℃, water inlet/outlet: 58℃/35℃
3. Cooling test condition: ambient temp: 35℃/24℃, water inlet/outlet: 20℃/15℃