- 20.3KW EVI Air source heat pump EVI low temperature Air to water heat pump ( heating +hot water )
- 【Brief】:
- 【Series】:Monoblock Low temperature EVI heat pump
- Description
-
Monoblock Low temperature EVI Air to water heat pump
Model
heat pump
FA-05EVI
Unit function
Standard condition
Heating capacity
kw
20.30
kcal/h
17455.00
Hot water supply
T/h
0.44
Input power
kw
4.80
Low temperature conditions
Heating capacity
kw
16.60
kcal/h
14273.00
Hot water supply
T/h
0.32
Input power
kw
4.69
Ultra-low temperature conditions
Heating capacity
kw
9.70
kcal/h
8340.00
Hot water supply
T/h
0.19
Input power
kw
4.15
Standard condition heating input current
A
8.40
Max running current
A
12.00
Power
V/Ph/Hz
380V/3N/50Hz
Unit Noise comprehensive index
Db(A)
58.00
Dimension
W
mm
810./1120
D
mm
780./425
H
mm
1050./1260
Unit weight
kg
145.00
Running control
Water temperature control precision
℃
±2℃
Ambient temperature range
℃
–25℃ – 43℃
Refrigerants circulation structure
Throttle type
thermostatic expansion valve/electric expansion valve
Refrigerant
Type
R407C,R410A
Refrigerant charge
kg
3.50
Max working pressure
bar
28.00
Compressor
Type
Efficient fully enclosed type vortex. Copeland,panasonic EVI
Stall Current
A
60.00
Air-source side heat exchanger
Type
Finned heat exchanger
Qty
pc
1.00
Motor power
kw
0.40
Hhot water side heat exchanger
Type
tube in shell heat exchange/plate heat exchange
Water flow
m3/h
3.49
Water pressure down
kPa
30.00
Connecting pipe size
DN
25.00
Water side max working pressure
kPa
1000.00
1,standard condition heating condiiton: air source side heat exchanger inlet air 20/15℃,hot water source intial temp 15℃,end heating temp 55℃.
2,Low temp heating condition: air source side heat exchanger inlet air 7/6℃,hot water side intial temp 10℃,end heating temp 55℃.
3,Ultra-low temperature heating conditions:air-source side heat exchanger inlet air -15/-17℃,hot water side intial temp 10℃,end heating temp 55℃.